Quantification of the association of ventilation rates with sick building syndrome symptoms

Publication Type
Conference Proceedings
Authors
Abstract

Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence with ventilation rate. For each study, slopes were calculated, representing the fractional change in SBS symptom prevalence per unit change in ventilation rate per person. Values of ventilation rate, associated with each value of slope, were also calculated. Linear regression equations were fit to the resulting data points, after weighting by study size. Integration of the slopeventilation rate equations yielded curves of relative SBS symptom prevalence versus ventilation rate. Based on these analyses, relative SBS symptom prevalence increases approximately 23% (12% to 32%) as the ventilation rate drops from 10 to 5 L/s-person and relative prevalence decreases approximately 29% (15% to 42%) as ventilation rate increases from 10 to 25 L/s-person.

Conference Name
Proceedings of the Indoor Air 2008
Year of Conference
2008
Conference Location
Copenhagen, Denmark, Paper 730
Custom 1
<p>1.2</p>
Keywords
Organizations
Research Areas
File(s)