Outdoor synthetic temperature for the calculation of space heating load

Date Published
01/1998
Publication Type
Journal Article
Authors
DOI
10.1016/S0378-7788(98)00013-9
Abstract

Methods to select the outdoor design temperature (ODT) for heating load calculation specified in current design codes in different countries are firstly discussed. Then a new method namely Stochastic Analysis is presented to determine the outdoor synthetic temperature (OST), which fully considers the randomness of weather and internal casual gains, and the thermal performance of buildings. The concept of OST enables the design of space heating system to be the trade-off between economics and risk. Finally, case studies of the influence of different building components on OST of a residential room in Beijing have been studied, which shows that OST depends upon building structures as well as weather conditions. It is recommended that OST rather than ODT should be employed in heating load calculation hence, sizing equipment for space heating systems.

Journal
Energy and Buildings
Volume
28
Year of Publication
1998
Issue
3
Pagination
269-277
Type of Article
Research Article
Keywords
Organizations
Research Areas
Download citation