Measured performance of filtration and ventilation systems for fine and ultrafine particles and ozone in an unoccupied modern California house
| Date Published |
12/2016
|
|---|---|
| Publication Type | Journal Article
|
| Authors | |
|---|---|
| DOI |
10.1111/ina.12359
|
| LBL Report Number |
LBNL-1006961
|
| Abstract |
This study evaluated nine ventilation and filtration systems in an unoccupied 2006 house located 250m downwind of the I-80 freeway in Sacramento, California. Systems were evaluated for reducing indoor concentrations of outdoor particles in summer and fall/winter, ozone in summer, and particles from stir-fry cooking. Air exchange rate was measured continuously. Energy use was estimated for year-round operation in California. Exhaust ventilation without enhanced filtration produced indoor PM2.5 that was 70% lower than outdoors. Supply ventilation with MERV13 filtration provided slightly less protection whereas supply MERV16 filtration reduced PM2.5 by 97-98% relative to outdoors. Supply filtration systems used little energy but provided no benefits for indoor-generated particles. Systems with MERV13-16 filters in the recirculating heating and cooling unit (FAU) operating continuously or 20 min/h reduced PM2.5 by 93-98%. Across all systems, removal percentages were higher for ultrafine particles and lower for black carbon, relative to PM2.5. Indoor ozone was 3-4% of outdoors for all systems except an electronic air cleaner that produced ozone. Filtration via the FAU or portable filtration units lowered PM2.5 by 25-75% when operated over the hour following cooking. The energy for year-round operation of FAU filtration with an efficient blower motor was estimated at 600 kWh/year. |
| Journal |
Indoor Air
|
| Year of Publication |
2016
|
| Organizations | |
| Research Areas | |
| File(s) | |
| Download citation | Google Scholar | DOI | BibTeX | Endnote tagged | RIS |