Harmonics from Compact Fluorescent Lamps
| Publication Type | Conference Paper
|
|---|
| Authors | |
|---|---|
| LBL Report Number |
LBL-33361
|
| Abstract |
Measured characteristics of compact fluorescent lamps (CFL) and incandescent lamps with diode type devices show low power factor (47% to 67%) and/or high total harmonic distortion (>100% THD). There is little effect on a building power quality if the CFL comprise less than 10% of the buildings load. Even if the load due to CFL is as high as 26% of the buildings total, the voltage distortion is less than 5%. Circuits along with estimated costs are presented that correct for power factor and suppress the harmonics. |
| Proceedings Title |
Annual IEEE-IAS Conference
|
| Conference Name |
Annual IEEE-IAS Conference
|
| Year of Publication |
1991
|
| Conference Location |
Dearborn, WI
|
| Call Number |
LBL-33361
|
| Organizations | |
| Research Areas | |
| File(s) | |
| Download citation |