Energy saving potential of a two-pipe system for simultaneous heating and cooling of office buildings
| Date Published |
01/2017
|
|---|---|
| Publication Type | Journal Article
|
| Authors | |
|---|---|
| DOI |
10.1016/j.enbuild.2016.10.051
|
| Abstract |
This paper analyzes the performance of a novel two-pipe system that operates one water loop to simultaneously provide space heating and cooling with a water supply temperature of around 22 °C. To analyze the energy performance of the system, a simulation-based research was conducted. The two-pipe system was modelled using the equation-based Modelica modeling language in Dymola. A typical office building model was considered as the case study. Simulations were run for two construction sets of the building envelope and two conditions related to inter-zone air flows. To calculate energy savings, a conventional four-pipe system was modelled and used for comparison. The conventional system presented two separated water loops for heating and cooling with supply temperatures of 45 °C and 14 °C, respectively. Simulation results showed that the two-pipe system was able to use less energy than the four-pipe system thanks to three effects: useful heat transfer from warm to cold zones, higher free cooling potential and higher efficiency of the heat pump. In particular, the two-pipe system used approximately between 12% and 18% less total annual primary energy than the four-pipe system, depending on the simulation case considered. |
| Journal |
Energy and Buildings
|
| Volume |
134
|
| Year of Publication |
2017
|
| Pagination |
234 - 247
|
| ISSN Number |
03787788
|
| Short Title |
Energy and Buildings
|
| Keywords | |
| Organizations | |
| Research Areas | |
| File(s) | |
| Download citation | Google Scholar | DOI | BibTeX | Endnote tagged | RIS |