The Effects of Fixture Type and HVAC Integration on Fluorescent Lamp-Ballast Performance
| Date Published |
10/1986
|
|---|---|
| Publication Type | Conference Paper
|
| Authors | |
|---|---|
| LBL Report Number |
LBL-21775
|
| Abstract |
This paper describes the effects of fixture type and lamp compartment air extract characteristics on lamp/ballast performance. A luminaire/plenum/HVAC simulator was used to measure minimum lamp wall temperature inside four fixture types while varying lamp-compartment extract conditions. Experimental data show that the lumen output of the lamp/ballast system varies by 20% and system efficacy by 10%, depending on the type of fixture and lamp compartment extract technique employed. |
| Proceedings Title |
1986 IEEE-IAS National Conference
|
| Conference Name |
1986 IEEE-IAS National Conference
|
| Year of Publication |
1986
|
| Conference Location |
Denver, CO
|