Behavior of Capstone and Honeywell Microturbine Generators During Load Changes
| Date Published |
07/2001
|
|---|---|
| Publication Type | Report
|
| Author | |
|---|---|
| LBL Report Number |
LBNL-49095
|
| Abstract |
This report describes test measurements of the behavior of two microturbine generators (MTGs) under transient conditions. The tests were conducted under three different operating conditions: grid-connect; stand-alone single MTG with load banks; and two MTGs running in parallel with load banks. Tests were conducted with both the Capstone 30-kW and Honeywell Parallon 75- kW MTGs. All tests were conducted at the Southern California Edison /University of California, Irvine (UCI) test facility. In the grid-connected mode, several test runs were conducted with different set-point changes both up and down and a start up and shutdown were recorded for each MTG. For the stand-alone mode, load changes were initiated by changing load-bank values (both watts and VARs). For the parallel mode, tests involved changes in the load-bank settings as well as changes in the power set point of the MTG running in grid-connect mode. Detailed graphs of the test results are presented. It should be noted that these tests were done using a specific hardware and software configuration. Use of different software and hardware could result in different performance characteristics for the same units. |
| Series Title |
Consultant Report prepared for the California Energy Commission
|
| Year of Publication |
2001
|
| Pagination |
38
|
| Institution |
CERTS
|
| City |
Rosemead
|
| Keywords | |