Analysis of fault-induced delayed voltage recovery using EMTP simulations

Date Published
07/2016
Publication Type
Conference Paper
Authors
DOI
10.1109/TDC.2016.7519960
LBL Report Number
LBNL-1006115
Abstract

This paper focuses on testing the dynamic behavior of single-phase air conditioner motors on distribution power networks. The primary goal is to study the phenomenon of delayed voltage recovery by applying multiple instances of a custom-built single-phase induction motor model on a given distribution feeder. This model was developed in an Electromagnetic Transients Program (EMTP) simulation environment. The motors were subjected to voltage disturbances seen in feeders experiencing the fault-induced delayed voltage recovery (FIDVR) phenomenon. To study the FIDVR phenomenon, a range of voltage depressions were simulated for predetermined system conditions. This paper describes a point-on-wave model development and simulation study that supports a broader investigation of the effect of air conditioning and similar loads on the recovery of electric utility voltage after faults.

Conference Name
IEEE Transmission and Distribution Conference
Year of Publication
2016
Publisher
IEEE
Organizations
Research Areas
Download citation