The Effects of Fixture Type and HVAC Integration on Fluorescent Lamp-Ballast Performance
Date Published |
10/1986
|
---|---|
Publication Type | Conference Paper
|
Authors | |
---|---|
LBL Report Number |
LBL-21775
|
Abstract |
This paper describes the effects of fixture type and lamp compartment air extract characteristics on lamp/ballast performance. A luminaire/plenum/HVAC simulator was used to measure minimum lamp wall temperature inside four fixture types while varying lamp-compartment extract conditions. Experimental data show that the lumen output of the lamp/ballast system varies by 20% and system efficacy by 10%, depending on the type of fixture and lamp compartment extract technique employed. |
Conference Name |
1986 IEEE-IAS National Conference
|
Year of Publication |
1986
|
Conference Location |
Denver, CO
|
Custom 1 |
<p>Lighting Systems Group</p>
|
Organizations | |
Research Areas | |
File(s) | |
Download citation |