Building Design: Impact on the Lighting Control System for a Daylighting Strategy

Date Published
10/1987
Publication Type
Conference Paper
Authors
LBL Report Number
LBL-22271
Abstract

This paper discusses the unique features of a multistory office building that successfully permit most of the space to be daylighted and the electric lights to be dimmed by a cost-effective centralized system. This system includes: the use of light shelves, sloped ceilings, and proper building orientation and symmetry, and supplies only the ambient illumination. Measurements of the daylight illumination levels and the performance of the lighting control system indicate that daylighting can provide over 70% of the required ambient illumination through the year. Based on the installed cost of the lighting control system, its payback period is 2.21 years.

Conference Name
1987 IEEE-IAS Annual Meeting
Year of Publication
1986
Conference Location
Atlanta, GA
Call Number
LBL-22271