Worker Performance and Ventilation: Analyses of Individual Data for Call-Center Workers

Publication Type
Conference Paper
Authors
LBL Report Number
LBNL-50124
Abstract

We investigated the relationship between ventilation rates and work performance in a call center. We randomized the ventilation controls and measured ventilation rate, differential carbon dioxide (ΔCO2) concentration, temperature, humidity, occupant density, degree of under-staffing, shift length, time of day, and time required to complete two different work performance tasks (talk and wrap-up). ΔCO2 concentrations ranged from 13 to 611 ppm. We used multi-variable regression to model the association between the predictors and the responses. We found that agents performed talk tasks fastest when the ventilation rate was highest, but that the relationship between talk performance and ventilation was not monotone. We did not find a statistically significant association between wrap-up performance and ventilation. At high temperatures agents were slower at both the talk and wrap-up tasks. Agents were slower at wrap-up during long shifts and when the call center was under-staffed.

Conference Name
Indoor Air 2002, June 30 - July 5, 2002
Volume
1
Year of Publication
2002
Pagination
796-801
Conference Location
Monterey, California
Keywords
Organizations
Research Areas