%0 Journal Article %K Distributed Energy Resources (DER) %K MG-TB001 %K Microgrid test bed %K Microgrids %A Robert H Lasseter %A Joseph H Eto %A Ben Schenkman %A John Stevens %A Harry T Volkommer %A David Klapp %A Ed Linton %A Hector Hurtado %A Joyashree Roy %B IEEE Transactions on Power Delivery %C Berkeley %D 2011 %N 1 %R 10.1109/TPWRD.2010.2051819 %T CERTS Microgrid Laboratory Test Bed %V 26 %2 LBNL-3553E %8 01/2011 %X

CERTS Microgrid concept captures the emerging potential of distributed generation using a system approach. CERTS views generation and associated loads as a subsystem or a "microgrid". The sources can operate in parallel to the grid or can operate in island, providing UPS services. The system can disconnect from the utility during large events (i.e. faults, voltage collapses), but may also intentionally disconnect when the quality of power from the grid falls below certain standards. CERTS Microgrid concepts were demonstrated at a full-scale test bed built near Columbus, Ohio and operated by American Electric Power. The testing fully confirmed earlier research that had been conducted initially through analytical simulations, then through laboratory emulations, and finally through factory acceptance testing of individual microgrid components. The islanding and resynchronization method met all Institute of Electrical and Electronics Engineers Standard 1547 and power quality requirements. The electrical protection system was able to distinguish between normal and faulted operation. The controls were found to be robust under all conditions, including difficult motor starts and high impedance faults. Keywords: CHP, UPS, distributed generation, intentional islanding, inverters, microgrid, CERTS, power vs. frequency droop, voltage droop.