%0 Conference Paper %A Liping Wang %A Philip Haves %A Walter F Buhl %B SimBuild 2012 IBPSA Conference %D 2012 %T An Improved Simple Chilled Water Cooling Coil Model %2 LBNL-6031E %8 08/2012 %X
The accurate prediction of cooling and dehumidification coil performance is important in model-based fault detection and in the prediction of HVAC system energy consumption for support of both design and operations. It is frequently desirable to use a simple cooling coil model that does not require detailed specification of coil geometry and material properties. The approach adopted is to match the overall UA of the coil to the rating conditions and to estimate the air-side and water-side components of the UA using correlations developed by Holmes (1982). This approach requires some geometrical information about the coil and the paper investigates the sensitivity of the overall performance prediction to uncertainties in this information, including assuming a fixed ratio of air-side to water-side UA at the rating condition. Finally, simulation results from different coil models are compared, and experimental data are used to validate the improved cooling coil model.