TY - CPAPER AU - Peng Xu AU - Philip Haves AB -

An automated fault detection and diagnosis tool for HVAC systems is being developed, based on an integrated, life-cycle, approach to commissioning and performance monitoring. The tool uses component-level HVAC equipment models implemented in the SPARK equation-based simulation environment. The models are configured using design information and component manufacturers' data and then fine-tuned to match the actual performance of the equipment by using data measured during functional tests of the sort using in commissioning. This paper presents the results of field tests of mixing box and VAV fan system models in an experimental facility and a commercial office building. The models were found to be capable of representing the performance of correctly operating mixing box and VAV fan systems and detecting several types of incorrect operation.

BT - 2002 American Council for an Energy-Efficient Economy Summer Study on Energy Efficiency in Buildings C2 - LBNL-50678 C3 -

80FJ53

C4 -

August 18-23, 2002

C5 -

CD

C6 -

Commercial Building Systems Group

C7 -

y

CN - LBNL-50678 CY - Pacific Grove, California DA - 05/2002 LA - eng N2 -

An automated fault detection and diagnosis tool for HVAC systems is being developed, based on an integrated, life-cycle, approach to commissioning and performance monitoring. The tool uses component-level HVAC equipment models implemented in the SPARK equation-based simulation environment. The models are configured using design information and component manufacturers' data and then fine-tuned to match the actual performance of the equipment by using data measured during functional tests of the sort using in commissioning. This paper presents the results of field tests of mixing box and VAV fan system models in an experimental facility and a commercial office building. The models were found to be capable of representing the performance of correctly operating mixing box and VAV fan systems and detecting several types of incorrect operation.

PP - Pacific Grove, California PY - 2002 T2 - 2002 American Council for an Energy-Efficient Economy Summer Study on Energy Efficiency in Buildings T3 - 2002 American Council for an Energy-Efficient Economy Summer Study on Energy Efficiency in Buildings TI - Field Testing of Component-Level Model-Based Fault Detection Methods for Mixing Boxes and VAV Fan Systems ER -