TY - CONF KW - Exposure KW - Indoor KW - Ventilation KW - Air pollution KW - Carbon dioxide KW - Performance KW - Demand-controlled ventilation KW - Mechanical ventilation KW - Calculating KW - Continuous operation KW - Occupancy KW - Sensors AU - Grenville K Yuill AU - Marc R Jeanson AU - Craig P Wray AB -
A central-supply ventilation system and a distributed-supply ventilation system were simulated to determine their relative performance in controlling occupant exposure to indoor air pollutants. Two different control strategies were used - (1) constant exhaust flow rates (continuous ventilation) and (2) modulations of the exhaust flow rates to keep the carbon dioxide concentration in the exhaust air stream constant (demand-controlled ventilation). The demand-controlled ventilation systems showed no clear advantage over the continuous ventilation systems. They reduced the exposures to some pollutants and increased the exposures to others. In some cases, the relative performance of the demand-controlled ventilation systems depended strongly on whether central-supply or distributed-supply ventilation was used.
BT - ASHRAE Transactions ET - 2 IS - Part 2 LA - eng N2 -A central-supply ventilation system and a distributed-supply ventilation system were simulated to determine their relative performance in controlling occupant exposure to indoor air pollutants. Two different control strategies were used - (1) constant exhaust flow rates (continuous ventilation) and (2) modulations of the exhaust flow rates to keep the carbon dioxide concentration in the exhaust air stream constant (demand-controlled ventilation). The demand-controlled ventilation systems showed no clear advantage over the continuous ventilation systems. They reduced the exposures to some pollutants and increased the exposures to others. In some cases, the relative performance of the demand-controlled ventilation systems depended strongly on whether central-supply or distributed-supply ventilation was used.
PY - 1991 SP - 963 EP - 968 ST - ASHRAE Trans. T2 - ASHRAE Transactions T3 - ASHRAE Transactions TI - Simulated Performance of Demand-Controlled Ventilation Systems using Carbon Dioxide as an Occupancy Indicator UR - http://www.techstreet.com/products/1717199 VL - 97 ER -