TY - CPAPER AU - Rudolph R Verderber AU - Oliver C Morse AU - Francis M Rubinstein AB -
Standard 40-watt, F-40, rapid-start, fluorescentslamps were operated with solid-state ballasts followingsthe standard life-testing cycle of 3 hours on ands20 minutes off for more than 20,000 hours at highsfrequency. Lamp operating characteristics (starting voltage, filament voltage, arc current, and current-crest factor) were studied as factors affecting lampslife. Measurements show that fluorescent lamps can attain rated life at high frequency using solid-state ballasts. When lamps are operated in the dimmedsnode, full filament power is required to sustain lampslife. The rate of lamp lumen depreciation is dependentson the lamp loading and not the operating frequency.
BT - Annual IEEE-IAS Conference C1 -Lighting Systems Group
C2 - LBL-19778 CN - LBL-19778 CY - Toronto, Canada DA - 10/1985 LA - eng N2 -Standard 40-watt, F-40, rapid-start, fluorescentslamps were operated with solid-state ballasts followingsthe standard life-testing cycle of 3 hours on ands20 minutes off for more than 20,000 hours at highsfrequency. Lamp operating characteristics (starting voltage, filament voltage, arc current, and current-crest factor) were studied as factors affecting lampslife. Measurements show that fluorescent lamps can attain rated life at high frequency using solid-state ballasts. When lamps are operated in the dimmedsnode, full filament power is required to sustain lampslife. The rate of lamp lumen depreciation is dependentson the lamp loading and not the operating frequency.
PP - Toronto, Canada PY - 1985 T2 - Annual IEEE-IAS Conference T3 - Annual IEEE-IAS Conference TI - Life of Fluorescent Lamps Operated at High Frequencies with Solid-State Ballasts ER -