@inproceedings{22615, keywords = {Offices, Perceived air quality, Improved IAQ practices and technologies, Ventilation rates and strategies}, author = {David Faulkner and William J Fisk and Douglas P Sullivan and Seung-Min Lee}, title = {Ventilation Efficiencies of a Desk-Edge-Mounted Task Ventilation System}, abstract = {
In chamber experiments, we investigated the effectiveness of a task ventilation system with an air supply nozzle located underneath the front edge of a desk and directing air toward a heated mannequin seated at the desk. The task ventilation system provided outside air, while another ventilation system provided additional space cooling but no outside air. Test variables included the vertical angle of air supply (-15° to 45° from horizontal), and the supply flow rate of (3.5 to 6.5 L s-1). Using the tracer gas step-up and step- down procedures, the measured air change effectiveness (i.e., exhaust air age divided by age of air at the mannequin's face) ranged from 1.4 to 2.7, which is higher than typically reported for commercially available task ventilation or displacement ventilation systems.
}, year = {2002}, journal = {Indoor Air 2002, June 30 - July 5, 2002}, pages = {1060-1065}, address = {Monterey, California}, language = {eng}, }