@proceedings{22270, keywords = {Indoor environment department, Ventilation, Airflow and pollutant transport group, Indoor airflow and pollutant transport, Cfd modeling, Contamination control, Downdraft table}, author = {Buvaneswari Jayaraman and Astrid H Kristoffersen and Elizabeth U Finlayson and Ashok J Gadgil}, title = {Investigation of Room Ventilation for Improved Operation of a Downdraft Table}, abstract = {
This paper reports a computational fluid dynamics (CFD) study on containment of airborne hazardous materials in a ventilated room containing a downdraft table. Specifically, we investigated the containment of hazardous airborne material under a range of ventilation configurations. The desirable ventilation configuration should ensure excellent containment of the hazardous material released from the workspace above the downdraft table. However, increased airflow raises operation costs, so the airflow should be as low as feasible without compromising containment. The airflow was modeled using Reynolds Averaged Navier Stokes equations with a high Reynolds number k-epsilon turbulence model using the commercial CFD code StarCD. CFD predictions were examined for several ventilation configurations. Based on this study, we found that substantial improvements in containment were possible with a significant reduction in airflow, compared to the existing ventilation configuration.
}, year = {2005}, journal = {Proceedings of The 10th International Conference on Indoor Air Quality and Climate - Indoor Air 2005}, volume = {3(1)}, pages = {2575-2579}, publisher = {Tsinghua University Press}, address = {Beijing, China}, language = {eng}, }